Thermal Break Strip Width for Aluminium Windows

Choose aluminium thermal breaks using paired frame specifications, PA66-GF25 material data and a worked 1.23 × 1.48 m window Uw comparison.

Two black insulating strips span the gap between hollow silver aluminium sections.
Answer in brief

Thermal Break Strip Width for Aluminium Windows

Choose thermal-break width with the full frame geometry and materials, because BS EN ISO 10077-2 determines Uf from the complete section rather than strip width alone.

The details behind the answer

For a 1.23 × 1.48 m window with 100 mm sightlines, Ug 1.1 W/(m²·K) and spacer ψg 0.040 W/(m·K), reducing assumed Uf from 2.5 to 1.0 W/(m²·K) gives calculated Uw 1.588 and 1.174 W/(m²·K), respectively.

Which frame dimensions actually accompany the strip?

One published 24 mm-strip system pairs a 60 mm frame with a 68 mm sash and accepts glazing up to 46 mm.

Published system configurationStrip width, mm / inFrame / sash depth, mm / inOpening-sash glazing, mm / inPublished thermal indicator, W/(m²·K)
a published 24 mm-break system24 / 0.9460 / 68 / 2.36 / 2.685–46 / 0.20–1.81Uw from 1.0, subject to size, glass and opening type
Standard-sash 34 mm-break family34 / 1.3470 / 79 / 2.76 / 3.1123–62 / 0.91–2.44Family Uf from 1.0
Concealed-sash 34 mm-break family34 / 1.3470 / 79 / 2.76 / 3.1118–54 / 0.71–2.13Family Uf from 1.5

How should 14.8, 24 and 34 mm fit into a system specification?

A published 24 mm-break system uses a 60 mm frame, a 68 mm sash and glazing from 5 to 46 mm. The 34 mm-break configurations come from a separate family brochure whose minima include enhanced-insulation variants; use the ordered variant for the final section calculation.

For a PA66-GF25 strip comparison, consider 14.8, 24 and 34 mm widths with 6 m stock lengths. Measure frame depth, sash depth and glazing pocket separately when comparing series numbers.

Keep aluminium profile wall thickness as a separate structural choice. A 5+20A+5 glass unit is 30 mm (1.18 in) thick, so its fit can be checked against the selected glazing pocket before the thermal calculation.

Follow the heat paths through a thermal-break frame
IMAGE NOTE

Strip geometry, cavities and the glazing edge form the complete thermal section.

How much can a 34 mm thermal break lower frame Uf?

Published minima are Uf 1.0 W/(m²·K) for one standard-sash family and 1.5 W/(m²·K) for its related concealed-sash family, covering different cavities, gaskets and sash arrangements.

Evaluate a proposed wider strip using the complete frame section under BSI's current BS EN ISO 10077-2 method. Include the polymer webs, cavities, inserts and glazing junction. Price the complete configuration that achieves the required Uf.

Calculate Uw with the same glass and frame area
IMAGE NOTE

Assumed frame Uf values of 2.5, 1.8 and 1.0 produce Uw values of 1.588, 1.395 and 1.174 W/(m²·K).

A 1.23 × 1.48 m example with fixed glazing and frame geometry compares three assumed frame Uf values and calculated whole-window Uw values of 1.588, 1.395 and 1.174.
IMAGE NOTE

With glass, spacer and geometry fixed, three assumed frame Uf values produce three different whole-window Uw values.

What Uw results from a 1.23 × 1.48 m window with Ug 1.1?

Assumptions: single-light design calculation, 1.23 × 1.48 m overall (48.43 × 58.27 in), uniform projected frame-and-sash width 100 mm (3.94 in), Ug = 1.1 W/(m²·K), warm-edge ψg = 0.040 W/(m·K), and assumed Uf cases of 2.5, 1.8 and 1.0 W/(m²·K).

The visible glass measures 1.03 × 1.28 m. Therefore Ag = 1.3184 m² (14.19 ft²), Af = 0.5020 m² (5.40 ft²), total area = 1.8204 m² (19.59 ft²), and glass-edge length lg = 4.62 m (15.16 ft).

Using the ISO 10077-1 whole-window calculation, Uw = (Ag × Ug + Af × Uf + lg × ψg) / (Ag + Af). Substitution gives Uw = (1.45024 + 0.5020 × Uf + 0.1848) / 1.8204.

Under these assumptions, Uw ≤ 1.4 requires Uf ≤ 1.820, and Uw ≤ 1.249 requires Uf approximately ≤ 1.273 W/(m²·K). Run the same equation for each 14.8, 24 or 34 mm candidate using its calculated section Uf. The U-value guide explains how frame, glass and edge losses combine.

With geometry, glass and spacer fixed, reducing assumed Uf from 2.5 to 1.0 lowers calculated Uw from 1.588 to 1.174 W/(m²·K).

Assumed frame UfCalculated Uw, W/(m²·K)Converted U, Btu/(h·ft²·°F)Relative to 1.4 / 1.249 W/(m²·K) benchmarks
2.51.5880.280Above both
1.81.3950.246Below 1.4, above 1.249
1.01.1740.207Below both

Which Part L and ENERGY STAR thresholds apply in November 2026?

For new or replacement windows in existing English dwellings, the 2021 Approved Document L incorporating 2023 amendments gives Uw ≤ 1.4 W/(m²·K), or Window Energy Rating Band B minimum. Its Table 4.2 and replacement-element provisions also require performance at least as good as the replaced element. England's official Part L guidance links both editions.

The 2026 edition takes effect on 24 March 2027 for work outside higher-risk building work and 24 September 2027 for higher-risk building work, subject to transition provisions. Its existing-dwelling window limit remains 1.4 or Band B. Use the project route in the UK window specification.

For US ENERGY STAR Version 7.0 Northern windows, the prescriptive limits are U-factor ≤ 0.22 Btu/(h·ft²·°F) and SHGC ≥ 0.17. The U-factor converts to approximately 1.249 W/(m²·K). The lowest assumed-Uf case clears that numerical benchmark. Certification uses the actual product's NFRC ratings and the other programme requirements.

The EPA criteria also allow Northern U-factors of 0.23 or 0.24 with SHGC ≥ 0.35, and 0.25 or 0.26 with SHGC ≥ 0.40. Select the destination through the ENERGY STAR climate-zone guide.

For Canada, Natural Resources Canada gives U-factor ≤ 1.22 W/(m²·K) or ER ≥ 34, with additional leakage and certification requirements. Align the order with the Canadian project specification.

What material details belong beside PA66-GF25?

PA66-GF25 denotes polyamide 66 with nominal 25% glass fibre. the thermal-barrier material supplier's material sheets list conductivity of 0.30 and 0.21 W/(m·K) for separate formulations, each with its own mechanical properties. the thermal-barrier material supplier data sheets

List GB/T 23615.1-2017 as the required material standard and record the polymer grade, specified raw-material origin, fibre content and batch identity in the purchase schedule. The standard remains current following its 2025 review. Pair material identification with the assembled profile's mechanical assessment.

Treat PVC, generic 'nylon' or an unnamed recycled mixture substituted into the quotation as a material change requiring qualification of the crimped connection. A declared recycled PA66-GF25 formulation can have its own thermal and mechanical data. Select the permitted grade against the purchasing specification and applicable standard. Keep whole-frame material choices in the aluminium-versus-uPVC comparison.

Is a polyamide strip the same as a poured-and-debridged thermal break?

FGIA describes 2 principal construction routes, polyamide strips and poured-and-debridged polyurethane. In a strip assembly, preformed profiles engage knurled aluminium pockets and are locked by rolling. In the poured route, liquid components are mixed and poured into a channel, cured, and the connecting metal bridge is removed.

The Fenestration and Glazing Industry Alliance's thermal-barrier guidance explains both processes. Its AAMA TIR-A8-16 covers composite framing's structural considerations, cavity design, material selection and performance testing. Select a compatible manufacturing process with the section.

What controls condensation at the inside frame?

Keep the inner frame and glass edge warmer than the indoor air's dew point through the selected thermal section, spacer and installation detail.

Control indoor moisture and airflow alongside those choices, using the window condensation diagnosis to distinguish room-side moisture from moisture between panes.

FAQ

Does a 60-series aluminium window necessarily contain a 24 mm strip?

One documented 60 mm frame uses a 24 mm thermal break and a 68 mm sash; another 60-series product still needs its own section geometry and glazing-pocket dimensions.

How much does frame performance change Uw when the glass stays the same?

At the stated 1.23 × 1.48 m dimensions and fixed glass-edge conditions, changing assumed Uf from 2.5 to 1.0 reduces calculated Uw by 0.414 W/(m²·K), about 26%.

What thermal break width do I need for U-factor 0.30 or Part L 1.4?

For whole-window U-factor 0.30 or Uw 1.4, strip width alone is insufficient; the complete frame, glazing and applicable rating method determine the result. U-factor 0.30 Btu/(h·ft²·°F) converts to about 1.70 W/(m²·K). For Uw 1.4 under the worked geometry and Ug 1.1, select a complete frame with Uf at or below approximately 1.820 W/(m²·K), then specify its matching strip width. The ISO-based worked example is not an NFRC-certified rating.

HAVE A PROJECT SCHEDULE?

Let YULUX review your drawings before pricing.

Send us your window schedule, floor plans or photos. We review opening sizes, system direction, glass, hardware, finish and packing scope before quoting.

Continue planning your window and door project

Glazing, thermal comfort and energy

Get a Quote

Share your window schedule, architectural drawings, opening sizes or a project brief. We'll reply with system, glass, hardware, finish and export packing recommendations.

YULUX chat

AI assistant · Human support
⋯

AI guidance only; our team confirms pricing. ·

I am an AI, not a person. Share non-sensitive project needs only. Answers and search sources need verification; I cannot confirm pricing, agency status or contracts. The temporary session is kept in this browser tab and server memory, and clears after 30 minutes of inactivity. Privacy policy

Hi, I’m YULUX’s AI assistant. Ask about products, window and door systems, or partnership.