CSA A440 and NAFS Window Ratings for Canadian Projects
A Canadian NAFS specification needs structural pressure and water resistance as separate values. Fenestration Canada's published label example has design pressure of ±1,620 Pa and water resistance of 240 Pa for an 800 × 1800 mm Class R, PG30 window. That NAFS-11/A440S1-17 example shows how to read the label; the building location sets the required performance.
Which NAFS and CSA A440S1 editions does NBC 2025 reference?
NBC 2025 Table 1.3.1.2 lists AAMA/WDMA/CSA 101/I.S.2/A440:22 and CSA A440S1:19. Its Articles 9.7.4.2 and 9.7.4.3 require the applicable product performance to suit the installation conditions and geographic location, with Performance Class R as the Part 9 minimum. NBC 2025, Division B
CSA published A440S1:25 for use with NAFS-22. Its published changes include a 20 m reference height in the simplified wind-load calculation and revised performance marking. The 2025 Supplement supersedes the 2019 publication, while the model code’s reference table still names the 2019 edition. Provincial or territorial legislation determines the code edition for each project. CSA A440S1:25 preface and scope
What does PG15 tell a Canadian window buyer?
The R-class entry grade is PG15, corresponding to approximately 720 Pa design pressure, and the project location can require a higher grade.
NAFS uses four classes, R, LC, CW and AW, with gateway requirements for product type, test dimensions and performance. PG covers structural resistance, water penetration, air leakage, operating force and forced entry under the applicable test set. FGIA performance classes
Window structural testing uses 150% of design pressure. Assumptions: design pressure 1,200 Pa. The structural test pressure is 1,800 Pa. The separately specified water pressure can still determine whether the proposed window suits the site. NBC 2025 Note A-9.7.4.2.(1)
Why does Canada specify water pressure separately?
For Canadian selection under NBC 2025, the site driving-rain wind pressure can be above or below 15% of design pressure, so the water rating must also satisfy the site requirement.
Location, height above grade and terrain exposure affect the required structural and driving-rain pressures. A coastal exposed elevation can need greater water resistance than a sheltered opening with the same structural target. The Supplement supplies the site-selection procedure. NBC 2025 water-resistance note
Assumptions: site design pressure 1,500 Pa and water requirement 300 Pa. A proposed window with design pressure 1,620 Pa and water resistance 240 Pa has sufficient structural pressure but a 60 Pa water shortfall. The purchase specification therefore needs positive design pressure, negative design pressure and water-test pressure as separate values.
Specify the site water pressure separately
What do the primary and secondary NAFS designations contain?
The primary designation includes Class, PG, tested dimensions and product type. The Canadian secondary designation reports positive and negative design pressure, water-test pressure and the Canadian air infiltration/exfiltration level. Canada already requires these secondary label values under the Supplement. NBC 2025 labeling note
The association’s historical label example uses Class R, PG30, tested size 800 × 1800 mm (31.5 × 70.9 in), type H, design pressures of ±1,620 Pa, water resistance 240 Pa and air level A3. It illustrates NAFS-11 with A440S1-17, so its example values belong to that configuration. Fenestration Canada 2021 label guide
FGIA states that NAFS-26 was published on June 1, 2026 and makes the secondary designator mandatory on reports and labels across that edition. The values include positive pressure, negative pressure and water-test pressure. NAFS-26 is absent from the NBC 2025 reference table. FGIA June 30, 2026 announcement
The NRC NBC 2020 guide gives maximum air leakage of 1.5 L/(s·m²) for A2 operable products and 0.2 L/(s·m²) for fixed products. Its published explanation covers the NBC 2020 framework. NRC NBC guide
Read both parts of a Canadian NAFS designation
Does a NAFS rating cover a larger window than the one tested?
A rating does not automatically extend to a larger window. FGIA requires testing at the largest size the manufacturer intends to certify and label. Smaller units must remain within the qualified design and configuration. FGIA tested-size explanation
Increasing width changes frame span, glass loading and hardware forces. A proposed 1,000 mm version needs qualification covering that width, even when an 800 mm version has been tested. Mullion, opening arrangement and glazing changes also need coverage within the qualified construction.
A combined fixed-and-operable assembly needs a performance basis for its joining mullion through testing or an applicable AAMA 450 method. The aluminum profile thickness guide covers material dimensions. The curtain wall versus window wall comparison covers façade-system selection. Fenestration Canada assembly guidance
Can Chinese or older Canadian grades be converted to NAFS?
GB/T 7106-2019 calculates classification air leakage at 10 Pa and evaluates both opening-joint length and specimen area.
Chinese classification takes the adverse result across three specimens and grades positive and negative pressures separately. Reports can show q1 in m³/(m·h) and q2 in m³/(m²·h). Converting 3.6 m³/(m²·h) to 1.0 L/(s·m²) changes the unit while retaining the 10 Pa test basis.
A Chinese grade or an older A/B/C classification has no numerical conversion into a Canadian NAFS grade. The required test methods, performance set, operating force and air-flow directions must be satisfied for the applicable edition. Canadian air levels describe infiltration and exfiltration, while US requirements differ. The historical A440 label alone supplies too little information for a new NAFS specification.
FAQ
Is CSA A440 still valid in Canada?
The A440 designation remains in the joint NAFS standard. NBC 2025 references AAMA/WDMA/CSA 101/I.S.2/A440:22 and CSA A440S1:19. Specify the referenced NAFS test set when assessing a product carrying an older standalone A440 A/B/C label.
Does NBC 2025 require CSA A440S1:25?
NBC 2025 Table 1.3.1.2 names A440S1:19. CSA has separately published A440S1:25 for NAFS-22. Apply the edition required by the project’s governing code and accepted specification.
Did Canada first require secondary NAFS labels in 2026?
Canada already required the secondary pressure values and Canadian air level through its Supplement. NAFS-26 makes the secondary designator mandatory across that new standard edition.