Sliding Door Threshold Accessibility by Code and Building Type
For a sliding door on an accessible route governed by the 2010 ADA Standards, a new threshold is limited to 1/2 inch (13 mm). The ADA level-change rules permit a vertical change up to 1/4 inch (6.4 mm); a change above 1/4 inch and up to 1/2 inch (13 mm) must be beveled no steeper than 1:2.
The details behind the answer
The threshold detail also has to work with the usable opening, operating effort, adjoining surfaces and the route that approaches the door.
Which threshold limit applies to your sliding door?
Start with the building use, the door's role in the accessible route and the edition adopted for the project. A public entrance, a dwelling entrance and a private balcony door can follow different provisions. Enter that classification beside the opening mark before choosing a sill section.
| Door and applicable scope | Maximum raised level | Additional dimension or gradient |
|---|---|---|
| US, new accessible-route door, 2010 ADA §404.2.5 | 1/2 in (13 mm) | Up to 1/4 in vertical; above 1/4–1/2 in bevel ≤1:2 |
| US, qualifying existing/altered threshold, same clause | 3/4 in (19 mm) | Bevel each side, no steeper than 1:2 |
| England, residential accessible threshold, M Volume 1 Appendix A | 15 mm | Upstands above 5 mm chamfered |
| England, unavoidable raised accessible entrance, M Volume 2 §2.7(e) | 15 mm | Upstands above 5 mm chamfered or rounded |
| China, actual doorway level difference, GB 55019 §2.5.3; no thresholds or doorstops | 15 mm | Transition no steeper than 1:10 |
Does ADA allow a higher threshold for every sliding door?
The 3/4 inch (19 mm) ADA allowance is for qualifying existing or altered thresholds with a bevel on each side no steeper than 1:2. Apply the exception according to the threshold's circumstances under the 2010 ADA threshold provision.
At a covered manual sliding door, check at least 32 inches (815 mm) clear opening and a maximum continuous opening force of 5 lbf (22.2 N) for a non-fire door under sections 404.2.3 and 404.2.9. The force provision excludes latch release and the initial force needed to overcome inertia. Section 404.2.7 also keeps sliding-door operating hardware usable from both sides when fully open.
Dimension the final passage with the leaf, handle and frame installed. A nominal frame width leaves the available passage unresolved. Record the finished floor levels on both sides and the highest obstruction in the actual wheel path. The designer should apply the relevant scoping provisions to the building and doorway.
For operating resistance found after installation, follow the sliding-door movement diagnosis alongside the threshold and hardware record.
Checks at a covered manual sliding door
How does England Part M treat patio and entrance doors?
The English residential accessible-threshold definition allows a total rise up to 15 mm, with any upstand above 5 mm chamfered. That definition appears in Appendix A of Approved Document M Volume 1, 2015 edition with 2016 amendments.
For a new dwelling subject to the optional M4(2) planning condition, paragraph 2.21 applies specified entrance provisions to other external doors, including those serving a garden, balcony or terrace. The 850 mm clear-opening requirement and accessible-threshold provision sit in paragraphs 2.20(d) and 2.20(h), as carried across by the residential Part M provisions.
For accessible entrances to buildings other than dwellings, Volume 2 prefers a level threshold. An unavoidable raised threshold is limited to 15 mm total, with upstands above 5 mm chamfered or rounded. Weather protection is part of the entrance guidance in the 2024-amended Volume 2.
Use these documents for England. Put the dwelling category and entrance designation on the same drawing as the threshold section. This lets the door fabricator and the local designer work from the same requirement when the surrounding terrace or balcony levels change.
What changes when the project uses Australia's NCC?
For the Queensland example checked on 11 November 2026, NCC 2022 continues to apply and NCC 2025 is scheduled to start on 1 May 2027. The state also retains its own variations, as set out in the Queensland adoption notice.
Take a new Class 1a house and identify its designated step-free entrance. Queensland requires at least 1 step-free entry for new homes within the applicable provisions and exemptions. Its QDC 4.5 changes effective from 14 August 2026 address accessible entry, surface-water protection and termite management together. See the state's Livable Housing Design Standard guidance.
Specify the accepted entrance solution as an assembly of the door, approach, landing and drainage. The August 2026 QDC 4.5 guideline explains how ramp options operate together with water-prevention and termite conditions. A ramp detail must therefore be checked with the associated conditions in the Queensland integrated-entry guidance.
For a Class 2 apartment, label the sole-occupancy entrance and shared accessible circulation separately. Add the state, building class and adopted code edition to the Australian project brief.
How can a low threshold drain without obstructing access?
Keep system drainage exits accessible for maintenance and clear of subsequent sealant or paving. The water-control detail should account for rain reaching the opening, water entering the designed track drainage and water accumulating on the approach. The large sliding-door track guide covers the associated panel and drainage configuration.
For accessible doors in China, GB 55019-2021 §2.5.3 first prohibits doorstops and thresholds. Where an actual doorway level difference exists, it must not exceed 15 mm and must have a beveled transition no steeper than 1:10. Section 2.2.4 limits grate openings on an accessible route to 13 mm, with elongated slots perpendicular to travel; both requirements appear in the Chinese accessibility standard.
After installation, record any specified water test against the completed threshold assembly using the site water-testing workflow. Include later changes to paving or drainage in the review, because those works can alter how water reaches the sill.
Coordinate the three paths at a low sill
Which details should travel with the door schedule?
The door schedule needs 5 entries: building and door classification, applicable code edition, clear opening, finished-level section and drainage interface. State the opening method and hardware alongside the threshold detail.
Compare lift-slide door configurations against that section. Keep the adopted dimensions attached to the project drawings through fabrication, installation and handover. A small change in the surrounding finish can change the height a user actually crosses.
Review the proposed sill section
Send the project location, building class, door schedule and finished-level section to discuss a sliding-door threshold configuration. Include the drainage arrangement and the access requirements set by the project designer.
FAQ
Is a 3/4-inch sliding-door threshold ADA-compliant?
The 3/4 inch (19 mm) allowance applies to qualifying existing or altered thresholds with bevels on both sides no steeper than 1:2. Covered new thresholds use the 1/2 inch (13 mm) limit.
What is the accessible threshold height in England?
For England dwellings, Volume 1 defines an accessible threshold with a maximum 15 mm rise and upstands above 5 mm chamfered; optional M4(2) extends specified entrance provisions to other external doors under §2.21. For accessible entrances to non-dwellings, Volume 2 prefers level access and permits an unavoidable rise up to 15 mm with upstands above 5 mm chamfered or rounded.
What must a threshold drawing show?
Show the user's wheel path, the door-system drainage outlet and the external surface-water drain on one section. Include the interior floor finish, exterior landing, drain inlet and discharge connection so changes in paving height remain visible.
Let YULUX review your drawings before pricing.
Send us your window schedule, floor plans or photos. We review opening sizes, system direction, glass, hardware, finish and packing scope before quoting.